ASHRAE 188 Quick Reference
ParameterLimit
HW heater outlet≥ 140°F (60°C)
Distal hot fixture≥ 122°F (50°C)
Recirc return≥ 124°F
Cold water supply≤ 68°F (20°C)
Free Cl₂ at distal≥ 0.2 ppm
Legionella growth zone68°F – 122°F
Cooling tower ORP≥ 650 mV
Pool / spa Cl₂≥ 3.0 ppm
Cooling tower Cl₂1.0 – 3.0 ppm
Note: NJ S2188 §2 consumer guidance cites ≥ 130°F for utility disruption notices only. WMP control limit is always 140°F per ASHRAE 188.